TM 5-5420-226-20-1
P r e v e n t i v e M a i n t e n a n c e C h e c k s a n d S e r v i c e s f o r M 4 8 A 5 A V L B H u l l -
Item
No.
47
Interval
Semiannual
Location
Item to
Check/Service
Fixed Fire
Extinguisher
System
- Continued
C o n t i n u e d
Procedure
Not Fully Mission
Capable if:
Step 13
If there is no CO2 discharge whatso-
ever, check for trapped high pressure
gas.
WARNING
Relieve system of high (800-1800 psi) pressure gas slowly. Wear gloves
and eye protection. Avoid breathing vapor. Failure to comply may
result in injury or death to personnel.
Loosen any fitting between delay
valve and check valve. If trapped gas
escapes, replace all three check
valves and repeat step 7.
If no gas escapes, tighten fitting.
Loosen any fitting between the CO2
cylinder and delay valve. If gas es-
capes, replace discharge delay bottle
assembly (page 20-57). Remove No. 1
CO2 cylinder (page 20-53). Tag cylin-
der and send to support maintenance
for recharging. Reset control handle
and reset control valve. Replace No.
1 CO2 cylinder (page 20-53). Repeat
steps 7 through 11.
Remove multimeter from accessory
test cable. Remove accessory test ca-
ble from engine accessory control
harness.
Reset control handle, reset control
valve and replace No. 1 CO2 cylin-
der.
Fixed fire extin-
guisher system
does not operate
properly.
Change 6 3-87